Fire extinguishing set of the dry pipe hose system must meet the conditions listed below in order to ensure proper operation of the system:
- the fire extinguishing set should from a separate fire sector and it should provide for safe access in the case of a fire,
- the supply line of the hydrant to the fire extinguishing set should be freeze-proof,
- the design of the sewage system has to provide for water drainage from the concrete bed of the fire extinguishing set,
- mechanical engineering design should envisage heating and ventilation of the fire extinguishing station,
- high-voltage design should provide for the following in the fire extinguishing set:
- power supply 220 V, 1 kW
- lighting
- electrical socket
- grounding of the set
- emergency lights above doors
- low-voltage design should ensure that the fire alarm signal and malfunction signal are transmitted to the a permanent control point.